100% unbalanced output, each phase
AC couple to retrofit existing solar system
*Max. 16 pcsparallel for on-grid and off-grid operation; Support multiple batteries parallel
Max. Charging/discharging current of 190A
6 time periods for battery charging/discharging
48V low voltage battery, transformer isolation design
Support storing energy from diesel generator
| Model | SUN-8K-SG05LP1-EU |
| Battery Type | Lead-acid or Lithium-ion |
| Battery Voltage Range (V) | 40-60 |
| Max. Charging Current (A) | 190 |
| Max. Discharging Current (A) | 190 |
| External Temperature Sensor | Yes |
| Charging Curve | 3 Stages / Equalization |
| Charging Strategy for Li-ion Battery | Self-adaption to BMS |
| PV String Input Data | |
| Max. PV Input Power (W) | 10400 |
| Max. PV Input Voltage (V) | 500 |
| Start-up Voltage (V) | 125 |
| MPPT Range (V) | 150~425 |
| Rated PV input voltage (V) | 370 |
| PV Input Current (A) | 26 + 26 |
| Max PV Isc (A) | 34 + 34 |
| No. of MPP Trackers | 2 |
| No. of Strings per MPP Trackers | 2 + 2 |
| AC Output Data | |
| Rated AC Output Active Power (W) | 8000 |
| Max. AC Output Apparent Power (A) | 8800 |
| AC Output Rated Current (A) | 36.4/34.8 |
| Max. AC Output Current (A) | 40/38.3 |
| Max. Continuous AC Passthrough (A) | 50 |
| Peak Power (off grid) | 2 times of rated power, 10s |
| Power Factor | 0.8 leading to 0.8 lagging |
| Output Frequency and Voltage | 50/60Hz; L/N/PE 220/230 |
| Grid Type | Single Phase |
| Total Harmonic Current Distortion (THDi) | <3% (of nominal power) |
| DC Current Injection | <0.5% In |
| Efficiency | |
| Max. Efficiency | 97.60% |
| Euro Efficiency | 97.00% |
| MPPT Efficiency | 99.90% |
| Protection | |
| Integrated | DC Reverse Polarity Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Arc Fault Circuit Interrupter (optional), Anti-islanding Protection, DC Switch, Insulation Impedance Detection, Residual Current Detection |
| Surge Protection | TYPE II(DC), TYPE II(AC) |
| Over Voltage Category | DC Type II/AC Type III |
| Certifications and Standards | |
| Grid Regulation | IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, |
| UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105 | |
| Safety EMC / Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |
| General Data | |
| Operation Temperature Range (°C) | -40-60°C, >45°C Derating |
| Cooling | Intelligent Air Cooling |
| Noise (dB) | ≤30 dB |
| Communication with BMS | RS485; CAN |
| Weight (kg) | 24.9 |
| Cabinet Size (WxHxD mm) | 330x580x232 (Excluding Connectors and Brackets) |
| Protection Degree | IP65 |
| Installation Style | Wall-mounted |
| Warranty | 3 Years(parts+service free) + 2 Years (service free) |